Kontaktorius 15kW LC1D32BD TeSys Deca, 3P(3NO), AC-3/AC-3e, <=440V, 32A, 24V DC ritė, varžtiniai kontaktai

  • Kraunamos nuotraukos
    Kodas: 035725
    Kaina 4610 be PVM
    (55 78  su PVM)
    Likutis: 26 vnt.
    Į krepšelį 
    Gamintojas
    Schneider Electric
  • Range of product
    TeSys D
    Product or component type
    Contactor
    Device short name
    LC1D
    Contactor application
    Motor control
    Resistive load
    Utilisation category
    AC-1
    AC-3
    Poles description
    3P
    Pole contact composition
    3 NO
    [Ue] rated operational voltage
    <= 690 V AC 25...400 Hz for power circuit
    <= 690 V DC for power circuit
    [Ie] rated operational current
    32 A (<= 60 °C) at <= 440 V AC AC-3 for power
    circuit
    50 A (<= 60 °C) at <= 440 V AC AC-1 for power
    circuit
    Motor power kW
    15 kW at 380...400 V AC 50/60 Hz
    7.5 kW at 220...230 V AC 50/60 Hz
    18.5 kW at 500 V AC 50/60 Hz
    18.5 kW at 660...690 V AC 50/60 Hz
    15 kW at 415...440 V AC 50/60 Hz
    Motor power hp
    2 hp at 115 V AC 50/60 Hz for 1 phase motors
    5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    7.5 hp at 200/208 V AC 50/60 Hz for 3 phases
    motors
    10 hp at 230/240 V AC 50/60 Hz for 3 phases
    motors
    20 hp at 460/480 V AC 50/60 Hz for 3 phases
    motors
    30 hp at 575/600 V AC 50/60 Hz for 3 phases
    motors
    Control circuit type
    DC standard
    Control circuit voltage
    24 V DC
    Auxiliary contact composition
    1 NO + 1 NC
    [Uimp] rated impulse withstand
    voltage
    6 kV conforming to IEC 60947
    Overvoltage category
    III
    [Ith] conventional free air thermal
    current
    50 A at <= 60 °C for power circuit
    10 A at <= 60 °C for signalling circuit
    Irms rated making capacity
    550 A at 440 V for power circuit conforming to IEC
    60947
    140 A AC for signalling circuit conforming to IEC
    60947-5-1
    250 A DC for signalling circuit conforming to IEC
    60947-5-1
    Rated breaking capacity
    550 A at 440 V for power circuit conforming to IEC
    60947
    [Icw] rated short-time withstand
    current
    138 A <= 40 °C 1 min power circuit
    260 A <= 40 °C 10 s power circuit
    430 A <= 40 °C 1 s power circuit
    60 A <= 40 °C 10 min power circuit
    100 A 1 s signalling circuit
    120 A 500 ms signalling circuit
    140 A 100 ms signalling circuit
    Associated fuse rating
    63 A gG at <= 690 V coordination type 1 for power
    circuit
    63 A gG at <= 690 V coordination type 2 for power
    circuit
    10 A gG for signalling circuit conforming to IEC
    60947-5-1
    The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
    This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
    It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
    Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
    1 / 3
    Average impedance 2 mOhm at 50 Hz - Ith 50 A for power circuit
    [Ui] rated insulation voltage 600 V for power circuit certifications CSA
    600 V for power circuit certifications UL
    690 V for power circuit conforming to IEC 60947-4
    1
    690 V for signalling circuit conforming to IEC
    60947-1
    600 V for signalling circuit certifications CSA
    600 V for signalling circuit certifications UL
    Power dissipation per pole 2 W AC-3
    5 W AC-1
    Protective cover With
    Mounting support Plate
    Rail
    Standards EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 508
    CSA C22.2 n°14
    Product certifications BV
    CCC
    CSA
    DNV
    GL
    GOST
    RINA
    UL
    LROS
    Connections - terminals Control circuit: screw clamp terminals 1 cable(s)
    1...4 mm² - cable stiffness: flexible - without cable
    end
    Control circuit: screw clamp terminals 2 cable(s)
    1...4 mm² - cable stiffness: flexible - without cable
    end
    Control circuit: screw clamp terminals 1 cable(s)
    1...4 mm² - cable stiffness: flexible - with cable end
    Control circuit: screw clamp terminals 2 cable(s)
    1...2.5 mm² - cable stiffness: flexible - with cable
    end
    Control circuit: screw clamp terminals 1 cable(s)
    1...4 mm² - cable stiffness: solid - without cable
    end
    Control circuit: screw clamp terminals 2 cable(s)
    1...4 mm² - cable stiffness: solid - without cable
    end
    Power circuit: screw clamp terminals 1 cable(s)
    2.5...10 mm² - cable stiffness: flexible - without
    cable end
    Power circuit: screw clamp terminals 2 cable(s)
    2.5...10 mm² - cable stiffness: flexible - without
    cable end
    Power circuit: screw clamp terminals 1 cable(s)
    1...10 mm² - cable stiffness: flexible - with cable
    end
    Power circuit: screw clamp terminals 2 cable(s)
    1.5...6 mm² - cable stiffness: flexible - with cable
    end
    Power circuit: screw clamp terminals 1 cable(s)
    1.5...10 mm² - cable stiffness: solid - without cable
    end
    Power circuit: screw clamp terminals 2 cable(s)
    2.5...10 mm² - cable stiffness: solid - without cable
    end
    Tightening torque Control circuit: 1.7 N.m - on screw clamp
    terminals - with screwdriver flat Ø 6 mm
    Control circuit: 1.7 N.m - on screw clamp
    terminals - with screwdriver Philips No 2
    Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Operating time 53.55...72.45 ms closing
    16...24 ms opening
    Safety reliability level B10d = 1369863 cycles contactor with nominal
    load conforming to EN/ISO 13849-1  

  • Prenumeruok ir laimėk

    Informacija